US Recessed Lighting Spacing, Ceiling Grid & NEC Circuit Load Calculator

Solve exact LED wafer and recessed can grids that satisfy both the Height / 2 anti-scallop spacing rule and room foot-candle targets. Toggle symmetric half-spacing or 30" kitchen counter-edge alignment, read printable (X, Y) laser coordinates, verify NEC 210.19 80% continuous load on 15A/20A circuits, and size 150W LED dimmers and Romex cable.

RECESSED FIXTURES 12 fixtures 4 cols × 3 rows · 4" LED Wafer
CENTER-TO-CENTER SPACING 3'-8" X · 3'-6" Y Wall offset 2'-6" X · 2'-6" Y (max 4'-0")
DELIVERED PHOTOMETRICS 9,000 lm 46.9 fc (target 40) · 19.07' floor cone
NEC 210.19 CIRCUIT LOAD 108W (0.9A) 7.5% of 15A 80% · 1x 150W dimmer

01 · ROOM & CEILING PARAMETERS

Room Type & Target Foot-Candles

Use 30" wall offset (2'-6") so downlights land over the front edge of 24" base cabinets without casting head shadows.

Recessed Fixture Type (Lumens, Watts & Beam)
Perimeter Wall-Offset Mode
NEC 210.19 Branch Circuit (120V)
SHEET E-101 · REFLECTED CEILING PLAN (RCP) GRID & BEAM OVERLAP8' CLG · 100° BEAM24" BASE CABINET COUNTER EDGELENGTH X = 16'-0"Y = 12'X OFF 2'-6"X O.C. 3'-8"2'-6"3'-6"4" LED FIXTUREBEAM OVERLAP (19.07' FLOOR)24" CABINET EDGEGRID 4x3 = 12 FIXTURES (9,000 LM)46.9 FC / ZERO DARK CORNERS108W / 1440W NEC 80%

EXACT (X, Y) CEILING LASER-LAYOUT COORDINATES

RowY from Top WallX Centers from Left Wall (4 fixtures/row)
Row 12'-6" (30")2'-6", 6'-2", 9'-10", 13'-6"
Row 26'-0" (72")2'-6", 6'-2", 9'-10", 13'-6"
Row 39'-6" (114")2'-6", 6'-2", 9'-10", 13'-6"

LIGHTING & NEC 210.19 ELECTRICAL TAKEOFF

Recessed Fixtures (4" Slim LED Wafer (750 lm / 9W)) 12 units (4 × 3)
Delivered Lumens vs. Kitchen Target (7,680 lm) 9,000 lm (46.9 fc)
Beam Cone Diameter (100° @ 8' clg) 19.07' floor / 13.11' counter
NEC 210.19 Circuit Load (15A 120V · 1,440W 80% cap) 108W (0.9A · 7.5%)
Remaining Continuous Circuit Headroom 1,332W available
LED-Rated Dimmer Switches (150W max LED load / dimmer) 1 dimmer
Estimated 14/2 NM-B Romex Cable (grid runs + switch drop + 20%) ~106 ft (1x 250' coil)
Recommended Color Temp & Housing Rating 3000K warm-neutral (90+ CRI) · IC/AT + Wet-Location
INCLUDED IN $19 5-SHEET VECTOR PDF EXPORT

Turn This Grid into a Scaled SHEET E-101 Electrical & Lighting Plan

Draft your room walls, cabinets, doors, and switched lighting zones in PlanCaliber Studio, then export a 5-sheet true-scale vector PDF pack (including SHEET E-101 Electrical & Lighting Plan), AutoCAD `.dxf`, 3D `.obj`, and itemized `.csv` takeoff for $19 one-time.

Draft Room & Sheet E-101 ->

Recessed Lighting Spacing by Ceiling Height (Height / 2 Rule)

Ceiling HeightMax Spacing (H / 2)Recommended Wall OffsetSuggested FixtureTypical US Room Use
7'-0"3'-6" max O.C.1'-9" (half spacing)4" or 6" Slim LED Wafer (100-110 deg)Finished basements, drop soffits, low hallways
8'-0"4'-0" max O.C.2'-0" std / 2'-6" kitchen4" 750 lm or 6" 1,000 lm LED WaferStandard US kitchens, bedrooms, home offices
9'-0"4'-6" max O.C.2'-3" std / 2'-6" kitchen6" 1,000 lm Wafer or 6" Baffled CanModern main-floor living rooms & primary baths
10'-0"5'-0" max O.C.2'-6" (half spacing)6" 1,200 lm Baffled IC/AT CanGreat rooms, open-concept kitchens, lofts
12'-0"6'-0" max O.C.3'-0" (half spacing)6" High-Output Can or 4" Gimbal (vaulted)Vaulted family rooms, bonus rooms, foyers

IECC R402.4.5 IC/AT & NEC 210.19 / 410.10(D) Installation Checklist

01

Height / 2 Spacing Rule: On a 8' ceiling, keeping fixtures within 4'-0" O.C. prevents ceiling scallops and dark floor corners.

02

Kitchen Cabinet Edge Alignment: Placing perimeter cans 30" (2'-6") off the drywall centers the beam over the front lip of 24" base cabinets and clears 12" upper wall cabinets.

03

NEC 210.19(A) 80% Continuous Load: A 15A 120V branch circuit (14/2 NM-B) is capped at 1,440W continuous (1,800W max). This layout draws 108W (7.5% of continuous capacity).

04

LED Dimmer Sizing: Most residential LED dimmers are rated for 150W max LED load (not 600W incandescent). This 108W array requires 1 dimmer switch (verify TRIAC/ELV compatibility).

05

IECC R402.4.5 Air-Tightness: Recessed fixtures penetrating an insulated attic ceiling must be IC-rated (Insulation Contact) and AT-rated (Air-Tight, <= 2.0 cfm air leakage at 75 Pa) with a gasketed trim.

06

Joist & Duct Conflict Check: Snap chalk or laser lines at exact (X, Y) coordinates before cutting drywall. Slim 1/2" LED wafers can mount directly beneath a 2x joist when a standard 6" can hits framing.

Recessed Lighting Spacing, Lumens & NEC Circuit Load FAQ

How far apart should recessed lights be spaced in an 8-foot ceiling?

Follow the Height / 2 spacing rule: divide the finished ceiling height by 2 to get the maximum center-to-center spacing. On a standard 8-foot ceiling, keep recessed fixtures at or under 4 feet (48 inches) on center, with perimeter fixtures placed 2 feet (half spacing) from drywall walls, or 30 inches from walls in kitchens with 24-inch base cabinets.

Why should kitchen recessed lights be 30 inches from the wall instead of half spacing?

Standard kitchen base cabinets are 24 inches deep and upper wall cabinets are 12 inches deep. Placing recessed lights 30 inches (2 feet 6 inches) off the finished wall centers the light beam directly over the front edge of the countertop, clearing upper cabinets and preventing your head and shoulders from casting shadows onto your prep workspace.

How many LED recessed lights can I put on a single 15-amp or 20-amp circuit under NEC 210.19?

Under NEC 210.19(A), continuous lighting loads cannot exceed 80% of the branch circuit rating: 1,440 watts on a 15A 120V circuit (14/2 NM-B Romex) or 1,920 watts on a 20A 120V circuit (12/2 NM-B Romex). At 9W to 12W per LED wafer, circuit capacity is rarely the bottleneck; instead, check your dimmer switch rating, since most residential LED dimmers are capped at 150W of LED load per switch.

What is the difference between 4-inch and 6-inch LED wafers?

4-inch slim LED wafers (typically 750 lumens, 9W) create a clean, uncluttered ceiling look and work well in kitchens, hallways, home offices, and bathrooms. 6-inch LED wafers (typically 1,000 lumens, 12W) offer wider 110-degree flood coverage, requiring fewer cutouts in larger living rooms and finished basements.

When are IC-rated, Air-Tight (AT), and Wet-Location recessed lights required?

Any recessed fixture penetrating an insulated attic ceiling must be IC-rated (Insulation Contact) and Air-Tight (AT) per IECC R402.4.5 to prevent fire hazards and conditioned air leakage. Fixtures installed directly above a tub or shower zone must be listed Wet-Location (IP65) per NEC 410.10(D).

How many lumens per square foot do I need for each room?

Target approximately 40 lumens per square foot (foot-candles) for kitchens, 45 lm/sq ft for bathrooms, 35 lm/sq ft for home offices, 25 lm/sq ft for basement rec rooms, 20 lm/sq ft for living rooms, and 15 lm/sq ft for bedrooms. Pairing bright target foot-candles with a 150W LED dimmer lets you dial the room from task brightness down to warm evening ambient light.

Preliminary Lighting & NEC Electrical Estimating Notice: This calculator provides preliminary recessed lighting spacing, reflected ceiling plan coordinates, photometric foot-candle estimates, and NEC 210.19 branch circuit load checks for US residential planning. Actual fixture counts, dimmer compatibility, joist/duct clearances, AFCI/GFCI protection, IECC R402.4.5 IC/AT air-sealing, and local NEC amendments vary by jurisdiction. Field-verify framing layout, wiring gauge, and electrical code compliance with a licensed electrician or local building authority before rough-in.