Size duplex receptacle counts, GFCI and AFCI protection requirements, and 15A or 20A
branch circuits across living rooms, bedrooms, kitchen countertops, bathrooms, garages,
and hallways with a live scaled 2D electrical schematic.
BRANCH CIRCUITS11 x 15A AFCI general branch circuit (max 8 outlets/circuit)
MAX SPACING RULEMax 6 ft from door/break, 12 ft O.C. max14'-0" x 12'-0" (46 LF usable)
Room Geometry & Circuit Parameters
NEC 2023
General Branch Circuit Rating
Kitchens, bathrooms, and garages require dedicated 20A branch circuits regardless of
general lighting circuit sizing.
Receptacle & Load Breakdown
Gross Perimeter
52 LF
Usable Wall Space
46 LF
General / Workbench Wall Outlets
5
Counter / Basin / Bay Outlets
0
Total Duplex Receptacles
5
Live 2D Electrical Schematic (Sheet E-101 Preview)
LAYER E-POWR
Auto-Generate Sheet E-101 & AutoCAD Layer E-POWR
Drafting in 2D/3D and saving a watermarked proof PNG are free. Unlock PlanCaliber's $19 Full CAD Pack to export Sheet E-101 (Electrical &
Lighting Plan) as a true-scale vector PDF plus an AutoCAD R12 .DXF with
layer E-POWR (ACI Yellow 2).
Spacing Rule: Max 6 ft from door/break, 12 ft O.C. max
Branch Circuit Planning: 1 circuit | 1 x 15A AFCI general branch circuit (max 8 outlets/circuit)
Preliminary space-planning & drafting worksheet. Verify all dimensions, structural spans, and local building codes on site with a licensed professional prior to construction.
NEC 2023 Section 210.52 Quick Reference
Room / Space
NEC Citation
Max Spacing Rule
Protection
Branch Circuit Baseline
Living / Bedroom / Den
210.52(A), 210.12
Max 6 ft from doorway/break; 12 ft O.C.; walls >= 2 ft
AFCI
15A or 20A general branch (8 to 10 outlets/ckt)
Kitchen & Countertops
210.52(C), 210.8(A)(6)
Max 24" from counter edge; 48" O.C. along countertop
GFCI + AFCI
Min 2 dedicated 20A Small-Appliance Circuits
Bathroom & Vanity
210.52(D), 210.11(C)(3)
Min 1 outlet within 36" of outside edge of each basin
GFCI
Min 1 dedicated 20A bathroom branch circuit
Garage / Workshop
210.52(G)(1), 210.11(C)(4)
Min 1 outlet per vehicle bay + 6 ft O.C. workbench wall
GFCI
Min 1 dedicated 20A garage branch circuit
Hallway (>= 10 ft)
210.52(H), 210.12
Min 1 outlet for hallways >= 10 ft (1 per 15 ft typical)
AFCI
Shared 15A or 20A general lighting/receptacle circuit
Electrical Outlet Spacing FAQ
What is the NEC 6-foot and 12-foot wall outlet spacing rule?
Under NEC 210.52(A), no point measured horizontally along the floor line of any usable wall space in living rooms, bedrooms, dens, or dining rooms may be more than 6 feet from a receptacle outlet. That results in a maximum spacing of 12 feet between wall outlets, and any continuous wall segment 2 feet or wider requires at least one receptacle.
How far apart must kitchen countertop outlets be spaced under NEC 210.52(C)?
Kitchen countertops require receptacles so no point along the wall line is more than 24 inches from an outlet, meaning countertop outlets are spaced no more than 48 inches (4 feet) apart. Kitchens also require at least two dedicated 20-amp Small-Appliance Branch Circuits with GFCI and AFCI protection.
Do bathroom and garage receptacles require dedicated 20-amp GFCI circuits?
Yes. NEC 210.52(D) and 210.11(C)(3) require at least one GFCI-protected receptacle within 36 inches of the outside edge of each bathroom basin on a dedicated 20-amp branch circuit. NEC 210.52(G)(1) and 210.11(C)(4) require at least one GFCI receptacle per vehicle bay in attached garages on a dedicated 20-amp garage branch circuit.
When does a residential hallway require a wall receptacle?
Per NEC 210.52(H), any hallway 10 feet or longer measured along the centerline must have at least one AFCI-protected receptacle outlet. Longer corridors typically place one outlet per 15 feet for practical vacuum and utility cord reach.
Preliminary Space-Planning Notice: This calculator provides preliminary
electrical outlet quantity and spacing estimates based on NEC 2023 Section 210.52 general
residential guidelines. Local amendments, adopted NEC edition year, kitchen island/peninsula
rules, and load calculations vary by jurisdiction. Always verify final electrical layouts
and panel capacity with your local Authority Having Jurisdiction (AHJ) and a licensed
electrician before rough-in or installation.