US Wood Stove Clearance, Hearth Pad & NFPA 211 Chimney 10-2-3 Rule Calculator
Size straight-wall and 45-deg corner wood stove clearances for UL 1482 listed and unlisted stoves, apply NFPA 211 ventilated 1" air-gap wall shield reductions (66% cut to 12" min),
dimension 16" front / 8" side hearth pads, and compute
exact 10-2-3 Class A chimney height above roof exit with > 5' roof brace alerts.
MATERIAL, CLEARANCE & CHIMNEY SCHEDULE
US Wood Stove Clearance, Hearth Pad & NFPA 211 Chimney 10-2-3 Schedule
- Stove & Placement: 24" W x 22" D · Straight Wall · UL 1482 Listed
- Combustible Wall Clearances: 12" rear / 16" side (No Shield) · Pipe: 6" (Double-Wall (6"))
- Minimum Hearth Pad: 40" W x 46" D (12.8 sq ft · 16" front / 8" sides & rear)
- NFPA 211 Chimney 10-2-3 Rule: 5.0' min above 6/12 roof exit (6' from ridge · 2 x 36" Class A sections)
Preliminary space-planning & drafting worksheet. Verify all dimensions, structural spans, and local building codes on site with a licensed professional prior to construction.
Lay Out Your Wood Stove Hearth, Furniture Clearances & Floor Plan in 2D/3D
Launch directly into PlanCaliber's free 2D/3D Studio to place your
40" x 46" hearth pad
(50" room projection) inside an A-frame cabin, living room, or
barndominium floor plan, and export scaled Vector PDF & AutoCAD .DXF sheets from $19 one-time.
NFPA 211 Wall Shield Clearance Reduction Reference Table
| Wall Protection Assembly | Air Gap | Max Reduction | From 36" Unlisted | NFPA 211 Installation Notes |
|---|---|---|---|---|
| Unprotected Combustible Wall (Drywall / Wood Studs) | None | 0% | 36" | Baseline NFPA 211 clearance for unlisted wood stoves; UL 1482 stoves follow listing plate. |
| 3.5" Solid Brick Masonry Directly Against Wall | None | 33% | 24" | Without a 1" ventilated air channel, solid brick conducts heat into framing and only permits 33% reduction. |
| 1/2" Cement Board on 1" Non-Combustible Spacers | 1" Ventilated | 50% | 18" | Non-combustible ceramic/steel spacers; keep bottom 1" open and top vented so convective air rises. |
| 24-Ga Sheet Metal on 1" Non-Combustible Spacers | 1" Ventilated | 66% | 12" Min | NFPA 211 Table 13.6.2.1 maximum wall reduction. Never place spacers directly behind the stove centerline. |
| 3.5" Brick Masonry on 1" Ventilated Air Space | 1" Ventilated | 66% | 12" Min | Requires 1" air cavity with open vents at base and top (or corrugated steel ties) to achieve full 66% cut. |
Wood Stove Hearth, Clearance & Chimney 10-2-3 Build Checklist
Verify the stove's permanent UL 1482 metal testing plate and owner manual before framing the hearth; manufacturer listed clearances always govern over generic tables.
Build the hearth pad to at least 40" wide x 46" deep (16" in front of the loading door, 8" sides/rear) and verify Type 1 ember vs Type 2 thermal R-value.
Maintain a 2" minimum air clearance around the Class A insulated chimney pipe through all ceiling joists, attic insulation shields, and roof rafters.
Measure the 10-2-3 chimney height from the high-side roof exit: confirm at least 5.0' above roof penetration (install storm collar, pitched roof flashing, and spark-arrestor cap).
Confirm local building department mechanical inspection and homeowner insurance wood-stove checklist requirements prior to first firing.
US Wood Stove Clearance, Hearth Pad & Chimney 10-2-3 FAQ
What is the NFPA 211 chimney 10-2-3 rule for wood stoves?
Under NFPA 211 and IRC R1003.9, a wood stove chimney must extend at least 3 feet above the highest point where it passes through the roof, AND at least 2 feet higher than any roof ridge, wall, or obstruction within 10 feet horizontally. On steep roofs (8/12 to 12/12) or penetrations far downslope from the ridge, the 10-foot horizontal rule often requires 6 to 10+ feet of Class A chimney pipe above the roof.
What is the minimum US hearth pad size for a wood-burning stove?
US NFPA 211 and IRC M1410 generally require non-combustible hearth floor protection extending at least 16 inches in front of the fuel-loading door and 8 inches beyond the sides and rear of the stove (18 inches front in Canada or where specified by the manufacturer). Always confirm whether your UL 1482 stove requires Type 1 ember-only protection or Type 2 thermal protection (R-1.1 to R-2.0).
How much does a ventilated wall shield reduce wood stove clearances?
Per NFPA 211 Table 13.6.2.1, a 24-gauge sheet metal shield or 3.5-inch solid brick wall mounted on 1-inch non-combustible spacers with open air channels at both the bottom and top reduces an unlisted stove clearance by up to 66%, from 36 inches down to a 12-inch minimum. For modern UL 1482 listed stoves, the stove testing plate governs and clearances cannot be reduced below the manufacturer manual.
When does a Class A wood stove chimney require a roof brace kit?
Most UL 103HT Class A insulated chimney manufacturers require an extended roof support brace kit whenever the chimney extends more than 5 feet above the roof flashing. On tall stacks (10+ feet), add an additional brace kit every 5 feet of exposed height to resist winter wind and sliding snow loads.
What is the difference between single-wall and double-wall stovepipe clearance?
Standard 24-gauge single-wall black connector pipe requires 18 inches of clearance to any combustible wall or ceiling. Listed double-wall insulated black connector pipe cuts that clearance to 6 inches to walls (and 8 inches to ceilings), which is essential when installing a modern UL-listed stove at 8-inch to 12-inch rear or corner clearances.