US Wood Stove Clearance, Hearth Pad & NFPA 211 Chimney 10-2-3 Rule Calculator

Size straight-wall and 45-deg corner wood stove clearances for UL 1482 listed and unlisted stoves, apply NFPA 211 ventilated 1" air-gap wall shield reductions (66% cut to 12" min), dimension 16" front / 8" side hearth pads, and compute exact 10-2-3 Class A chimney height above roof exit with > 5' roof brace alerts.

Open Cabin / Room Plan in 2D/3D Studio ->
PRESETS:
CHIMNEY 10-2-3 HEIGHT 5.0 ft above exit Self-supporting (<= 5 ft) · 2 × 36" Class A
WALL CLEARANCE 12 in min Rear 12" · Side 16" · No Shield
MINIMUM HEARTH PAD 40" × 46" 12.8 sq ft · 16" front / 8" sides & rear
FLUE PIPE & PROJECTION 6 in pipe Double-wall connector · 50" projection
INPUTS · STOVE, SHIELD & ROOF STRAIGHT WALL
Placement Geometry Straight Wall
Stove Listing UL 1482 Listed
NFPA 211 Wall Heat Shield Unshielded
Connector Stovepipe Type 6" clearance
Roof Pitch (Rise / 12) 6/12 (26.6°)
NFPA 211 / IRC SUMMARY
Governing Rule 2-ft above ridge (within 10-ft horizontal zone)
Hearth Thermal Spec Type 1 / Check UL Plate
Wall Projection 50" (4.2')
Roof Brace Kit Not Required
SHEET M-104 · WOOD STOVE CLEARANCE, HEARTH PAD & NFPA 211 CHIMNEY 10-2-3 5.0' STACK
PLAN VIEW · HEARTH & CLEARANCESTRAIGHT WALLCOMBUSTIBLE REAR WALLREAR: 12" MINSIDE: 16"PIPE: 6"24"x22"WOOD STOVE16" FRONT EMBER APRON8" SIDES & 8" REAR PADHEARTH: 40" W x 46" D (12.8 SF)WALL-TO-FRONT PROJECTION: 50"ELEVATION · CHIMNEY 10-2-3 RULE6/12 PITCHMIN STACK: 5.0' ABOVE EXITSELF-SUPPORT (<= 5')10-2-3 RULE: >= 3' ABOVE EXIT & >= 2' ABOVE ROOF WITHIN 10'6.0' FROM RIDGE · 2 x 36" CLASS A PIPE SECTIONSNFPA 211 / IRC 10-2-3 COMPLIANT · 5.0' STACK · 12" WALL CLEARANCEPLANCALIBER CALC-45 · US WOOD STOVE CLEARANCE, HEARTH & CHIMNEY 10-2-3 REFERENCESHEET M-104

MATERIAL, CLEARANCE & CHIMNEY SCHEDULE

Clearance Rear Combustible Wall Clearance
UL 1482 Listed · No Shield · Side wall clearance: 16" min · Total room projection to hearth front: 50"
12" min
Clearance Flue Connector Pipe Clearance
Double-Wall Black Connector · Listed double-wall black stovepipe from flue collar to ceiling support box
6" min
Hearth Rectangular Straight-Wall Hearth Pad
Type 1 Ember Pad (verify UL plate for Type 2 R-1.1/R-1.5) · Includes 16" front fuel-door ember apron + 8" sides & 8" rear
40" W x 46" D (12.8 sq ft)
Chimney Class A Insulated Chimney Stack (UL 103HT)
6/12 roof · 6' from ridge · 2-ft above ridge (within 10-ft horizontal zone) · Within 5 ft self-supporting limit: include pitch flashing, storm collar & spark-arrestor rain cap
5.0' min (2 x 36" pipes)
2D/3D CABIN, LIVING ROOM & BARNDOMINIUM STUDIO · VECTOR PDF & DXF

Lay Out Your Wood Stove Hearth, Furniture Clearances & Floor Plan in 2D/3D

Launch directly into PlanCaliber's free 2D/3D Studio to place your 40" x 46" hearth pad (50" room projection) inside an A-frame cabin, living room, or barndominium floor plan, and export scaled Vector PDF & AutoCAD .DXF sheets from $19 one-time.

NFPA 211 Wall Shield Clearance Reduction Reference Table

Wall Protection AssemblyAir GapMax ReductionFrom 36" UnlistedNFPA 211 Installation Notes
Unprotected Combustible Wall (Drywall / Wood Studs)None0%36"Baseline NFPA 211 clearance for unlisted wood stoves; UL 1482 stoves follow listing plate.
3.5" Solid Brick Masonry Directly Against WallNone33%24"Without a 1" ventilated air channel, solid brick conducts heat into framing and only permits 33% reduction.
1/2" Cement Board on 1" Non-Combustible Spacers1" Ventilated50%18"Non-combustible ceramic/steel spacers; keep bottom 1" open and top vented so convective air rises.
24-Ga Sheet Metal on 1" Non-Combustible Spacers1" Ventilated66%12" MinNFPA 211 Table 13.6.2.1 maximum wall reduction. Never place spacers directly behind the stove centerline.
3.5" Brick Masonry on 1" Ventilated Air Space1" Ventilated66%12" MinRequires 1" air cavity with open vents at base and top (or corrugated steel ties) to achieve full 66% cut.

Wood Stove Hearth, Clearance & Chimney 10-2-3 Build Checklist

01

Verify the stove's permanent UL 1482 metal testing plate and owner manual before framing the hearth; manufacturer listed clearances always govern over generic tables.

02

Build the hearth pad to at least 40" wide x 46" deep (16" in front of the loading door, 8" sides/rear) and verify Type 1 ember vs Type 2 thermal R-value.

03

Maintain a 2" minimum air clearance around the Class A insulated chimney pipe through all ceiling joists, attic insulation shields, and roof rafters.

04

Measure the 10-2-3 chimney height from the high-side roof exit: confirm at least 5.0' above roof penetration (install storm collar, pitched roof flashing, and spark-arrestor cap).

05

Confirm local building department mechanical inspection and homeowner insurance wood-stove checklist requirements prior to first firing.

US Wood Stove Clearance, Hearth Pad & Chimney 10-2-3 FAQ

What is the NFPA 211 chimney 10-2-3 rule for wood stoves?

Under NFPA 211 and IRC R1003.9, a wood stove chimney must extend at least 3 feet above the highest point where it passes through the roof, AND at least 2 feet higher than any roof ridge, wall, or obstruction within 10 feet horizontally. On steep roofs (8/12 to 12/12) or penetrations far downslope from the ridge, the 10-foot horizontal rule often requires 6 to 10+ feet of Class A chimney pipe above the roof.

What is the minimum US hearth pad size for a wood-burning stove?

US NFPA 211 and IRC M1410 generally require non-combustible hearth floor protection extending at least 16 inches in front of the fuel-loading door and 8 inches beyond the sides and rear of the stove (18 inches front in Canada or where specified by the manufacturer). Always confirm whether your UL 1482 stove requires Type 1 ember-only protection or Type 2 thermal protection (R-1.1 to R-2.0).

How much does a ventilated wall shield reduce wood stove clearances?

Per NFPA 211 Table 13.6.2.1, a 24-gauge sheet metal shield or 3.5-inch solid brick wall mounted on 1-inch non-combustible spacers with open air channels at both the bottom and top reduces an unlisted stove clearance by up to 66%, from 36 inches down to a 12-inch minimum. For modern UL 1482 listed stoves, the stove testing plate governs and clearances cannot be reduced below the manufacturer manual.

When does a Class A wood stove chimney require a roof brace kit?

Most UL 103HT Class A insulated chimney manufacturers require an extended roof support brace kit whenever the chimney extends more than 5 feet above the roof flashing. On tall stacks (10+ feet), add an additional brace kit every 5 feet of exposed height to resist winter wind and sliding snow loads.

What is the difference between single-wall and double-wall stovepipe clearance?

Standard 24-gauge single-wall black connector pipe requires 18 inches of clearance to any combustible wall or ceiling. Listed double-wall insulated black connector pipe cuts that clearance to 6 inches to walls (and 8 inches to ceilings), which is essential when installing a modern UL-listed stove at 8-inch to 12-inch rear or corner clearances.

Preliminary NFPA 211 / IRC wood stove clearance and chimney height estimate only. Listed stoves follow the manufacturer's permanent UL 1482 testing plate; verify your exact stove manual, local building department mechanical permit rules, and homeowner insurance inspection requirements before installing.